Eurotherm
Invensys Operations Management
.

DIN Rail Mounted Mini Input/Output Modules – IO Series

The IO Series of Mini Input/Output mod280ules provide a high density, DIN Rail mountable device for low power heating loads or conversion of ac or dc control logic levels to a low level dc signal.

 

Mini IO Mechanical Details
Mini IO Series
Shop Online

IDEAL FOR:

  • Industrial and commercial ovens
  • Injection molding machines
  • Induction Furnaces
  • Solenoid/Valve Drivers
  • Semiconductor manufacturing equipment
  • Food processing
  • Motor Controls
  • ATM Machines
  • Battery Chargers
  • Mercury Relay Replacements

FEATURES:

  • 3 amps 12-280V ac

  • High density design

  • AC and DC inputs

  • AC and DC outputs

    Positive and negative logic

  • Single phase zero crossing

  • LED logic indicator

  • Output modules internally fused

  • Optically isolated

    4000 VRMS isolation on all model numbers

  • CE compliant

  • UL recognized

  • CSA certified

Specifications 

 

   
Input Modules     

YELLOW CASE

IO-IAC/-RO/280

IO-IAC/+RO/280 

Output Voltage Range:

4-28V dc

4-28V dc

Max Load Current:

100mA

100mA

Turn On Time:

20ms max

20ms max

Turn Off Time:

20ms max

20ms max

Input Voltage:

90-280V ac

90-280V ac

Logic Type:

Negative

Positive

 

 

 

WHITE CASE

IO-IDC/-RO/280

IO-IDC/+RO/280

Output Voltage Range:

4-28V dc

4-28V dc

Max Load Current:

100mA

100mA

Turn On Time:

30μs max

30μs max

Turn Off Time:

60μs max

60μs max

Input Voltage:

4-28V dc

4-28V dc

Logic Type:

Negative

Positive

   

 

Output Modules  

 

BLACK CASE

IO-OAC/RO/280

IO-OAC/RA/280 

Input Voltage Range:

4-28V dc

90-280V ac

Logic Input Impedence:

1,500ohms

40,000ohms

Output Voltage Range:

12-280V ac

12-280V ac

Output Current Range:

.10-3ARMS @ 40°C (1)

.10-3ARMS @ 40°C (1)

Leakage Current:

5mA @ field voltage

5mA @ field voltage

   

 

RED CASE

IO-ODC/RO/060 (2)

IO-ODC/RL/060 (3)  

Input Voltage Range:

4-28V dc

4-28V dc

Logic Input Impedence:

1,500ohms

1,500ohms

Output Voltage Range:

5-60V dc

5-60V dc

Output Current Range:

0-3ARMS @ 40°C (1)

0-3ARMS @ 40°C (1)

Leakage Current:

1mA @ max field voltage

100μA @ max field voltage

   

 

Notes

(1) The 3 amp output is obtained when there is <40°C ambient air surrounding all sides of the module. Derate the output if the ambient temperature is higher or if the modules are tighly stacked together.

(2) Turn On Time - 40μs, Turn Off Time - 40μs

(3) Turn On Time - 50μs, Turn Off Time - 100μs  

 